Operation “A” Ending – Part II

(In VCB type 5-branches DJ provided locos only) Abnormal Sign: Close BLDJ and press BLRDJ. LSDJ extinguishes. UA meter needle deviates. Sound comes from the auxiliaries. LSCHBA also extinguishes. While releasing BLRDJ, LSDJ re-glows. Cause: Defective DJ N/O I/L on MTDJ branch. Troubleshooting: Take advice from TLC.

its test

Attention Passengers! 🚨 🚧 Mega Block on Up & Down Main lines and Harbour line on 01.09.2024 (Sunday). Check the schedule for first and last locals before and after the block. Plan your travel accordingly.#MegaBlock #SundayBlock pic.twitter.com/Ox8mUgJ8tY — Central Railway (@Central_Railway) August 31, 2024

Operation A Beginning

Explanation:

While closing DJ, if there is any earth fault or overcurrent in the auxiliary power circuit, or if the pressure drops below the QPDJ set value, or there is a cut in the MTDJ coil, the MTDJ coil will de-energize and DJ will trip immediately after closing.

Operation A Ending part-1

Abnormal Signs:

Close BLDJ, press BLRDJ: Attempting to close the main circuit breaker (DJ).

LSDJ extinguishes: DJ closes.

UA needle deviates: Indication of auxiliary power activity.

Auxiliary sound may or may not be heard: Audible indication of auxiliary machinery starting.

LSCHBA does not extinguish: Specific indicator light does not turn off.

LSDJ glows again after 5.6 sec (DJ trips) before BLRDJ is released: DJ trips shortly after being closed.